Outdoor control box temperature and humidity regulator



It is suitable for adjusting temperature and humidity of all kinds of control cabinets, electrical cabinets and other similar electrical equipment or cabinets in outdoor environment. Such as: outdoor transformer preset box, communication cabinet, energy storage equipment, charging pile, power cabinet, etc.

■ The main features

1, the whole series of environmental refrigerant, large circulating air volume, long distance air supply, suitable for all kinds of outdoor box (cabinet) application occasions.

2. Overall maintenance-free design and unique rainproof structure design, protection grade 1IP55, strong corrosion resistance, clean appearance, beautiful appearance, reliable performance.

3, special microcomputer controller, fully functional, digital temperature display, automatic cooling and heating control, with hydrogen exhaust fan control function, optional RS485 communication function (support general electric protocol, MODBUS protocol).

4, with multiple protection function and alarm no contact alarm function, failure code display.

5. Heating function is standard for all series models.


■ Specifications and parameters

model

LA-12Q-W

LA-15Q-W

LA-20Q-W

LA-25Q-W

LA-32Q-W

LA-40Q-W

LA-50Q-W

Cooling capacity(W)

1200

1500

2000

2500

3200

4000

5000

The power supply

1P~220V 50Hz

Rated power(W)

590

640

1000

1185

1420

2030

2300

Rated current(A)

3.1

3.3

4.6

5.5

6.6

9.6

13.5

refrigerant

R134a

Ambient temperature range(ºC)

-20~50

protective
level

Inner loop

IP54

Outer loop

IP44

Overall dimensions
(width × height × thickness)
(mm)

455×1040
×270

455×1040
×270

455×1370
×295

455×1420
×355

505×1490
×315

540×1650
×325

540×1650
×345


1. The cooling capacity is based on the inlet air temperature of 35ºC and the in-box temperature of 35ºC;

2. The compressor will not start when the ambient temperature is lower than 10℃;

3, can be customized according to user needs special power system model, specific parameters please consult the manufacturer.

4. If you need communication interface and communication protocol, please consult and indicate the requirements in time.